Novrel - RMT-230T Langallinen 230V s. 1
Data Sheet
Electro-Mechanical Room Thermostat RMT
Application
RMT room thermostats are suitable for the control of heating, ventilation and air conditioning systems. The range includes models for use in 24V systems - types RMT 24, RMT 24T and RMT 24R, plus models for use in 220/240V systems - types RMT 230 and RMT 230T. Versions are also available with built-in thermometer and night set-back function. Please refer to tables below for technical specifications and ordering codes.
Principle
Ordering
No. 1 2 3 4 5 6
Type RMT-230 RMT-230 * RMT-230T RMT-24 RMT-24T RMT-24R 1)
Ordering Code 087N1100 087N1110 087N1125 087N1196 087N1197 087N1195 087N0099
Description 230V a.c. 230V a.c. 230V a.c. 24V a.c. 24V a.c.
Accelerator Parallel No Parallel Parallel Parallel
Thermometer No No Yes No Yes No
Night Setback No No Yes No Yes Yes
24V a.c. Parallel Adaptor plate for flush mounting * No accelerator heater
1) Only to be used with actuator ABN-NO
Data
Temperature Range °C Contact Type Contact Material Contact Rating, Ohmic A a.c. Contact Rating, Inductive cos ϕ = 0.6A a.c. Contact Rating, Start Current A a.c. Contact Rating, Ohmic A d.c. Contact Rating, Minimum mA a.c./mA d.c. Thermal Deviation °K Cut in Stability °K Time Constant Vair = 0.15m/sec) min Thermal Differential °K (with accelerator) Storage Temperature Range Working Temperature Range Air Humidity % RH Weight g Protection Class
RMT-24 8 - 30 SPDT Ag 10 4 24 1 70 < 2.5 < 0.5 < 14 < 1.0 -20 - +50 -10 - +50 40-60 150 IP 20
RMT-230 8 - 30 SPDT Ag 10 4 24 150 < 2.5 < 0.5 < 14 < 1.0 -20 - +50 -10 - +50 40-60 150 IP 20